Network outage after scheduled router maintenance
What customers saw
From 4:30 AM Pacific on November 2, the website, portal, backup vaults, Borg repositories, servers and payments could not be reached from the internet. Most services returned at 7:15 PM the same day. Proxmox offsite datastores returned at 9:45 PM on November 3.
Root cause
Our edge router was restarted during scheduled maintenance to apply CPU security mitigations. At boot, one firewall rule referred to a network interface before that interface existed, so the whole ruleset was rejected and the router came up without its forwarding rules.
The Proxmox offsite storage pool did not reattach on its own after the host restart, which kept those datastores offline longer.
Why recovery took hours
The router is the path every remote connection uses, including ours. With it down, the fix needed hands-on access at the facility.
What we changed
The router now checks its configuration before loading it and falls back to the last configuration that worked. Restarts of network equipment are blocked until an automated readiness check passes.
This status page now runs on separate infrastructure outside our facility, so it stays up when we do not.
Data impact
None. No stored data was lost or exposed. Backups scheduled during the outage could not connect and ran on their next schedule once service returned.
Credits
Customers whose monthly availability fell below our SLA target received the published service credit automatically. It is applied to the next invoice.